Thermal & envelope

Room Air-Conditioner Size

The peak cooling load of one room, or of several rooms on one ducted unit, in watts, Btu/h and tons, hour by hour on the 21 July design day in 27 Saudi cities: the unit to buy, the air each room needs, and the room or the whole plan in 3D.

ASHRAE Handbook: FundamentalsSASO 2663:2021Metric

An hour-by-hour cooling load on the ASHRAE clear-sky design day, 21 July, from 6 to 18 solar time, with the design conditions of 27 Saudi weather stations from the 2025 ASHRAE Handbook: Fundamentals. Every exterior wall and an exposed roof conducts heat at its sol-air temperature, windows add conduction and solar gain through their SHGC, and people (ASHRAE Table 3), lighting, equipment and outdoor air add the rest, sensible and latent; the load is checked again at the design wet bulb, the most humid hot hours. For one room, the hour with the highest total plus your design margin is the capacity to buy, turned into a wall split, a floor-standing unit, a cassette, a ducted unit or a window unit. For several rooms on one unit (a villa floor or an office) you list the rooms on each side of a corridor; the page draws the plan, finds which part of each wall faces outside, adds the rooms hour by hour and sizes the ducted unit on the largest sum, with the supply air each room needs and the wall split each room would need on its own.

Location and design conditions

The share of the year's hours hotter than the design value (ASHRAE Handbook: Fundamentals 2009, Ch. 14); 0.4% is the most demanding.

The design day is 21 July, so the northern hemisphere only (0 to 60°).

The load is also computed at the design wet bulb with its mean coincident dry bulb (the most humid hot hours) and the larger peak sets the size. Leave both empty to skip the check.

Room, walls and windows

Walls: tick the exterior ones and enter their windows

1.0 = no internal shading. Enter your own factor for blinds or curtains.

Wall and roof construction

From the U-value calculator or the supplier's data.
From the U-value calculator or the supplier's data.

People and internal gains

Your own figure: installed lamp watts ÷ floor area.
Your own figure: the nameplate watts of what runs at the same time (TV, computers, fridge).
Your own figure; 0.5 by default.
Mechanical fresh air, if any; 0 by default.
24 °C and 50% by default.
0.2 by default; light paving and sand reflect more.
10% by default, on the total.

What to buy

The room and the chosen unit

From the model's specification sheet; leave 0 if you do not have it.

The load hour by hour on 21 July

    Steady-state load on the clear-sky design day, solar hours 6 to 18: outdoor air at the design dry bulb all day, sol-air on every sunlit surface, no credit for thermal storage.

    Component by component at the peak hour

    Component Area / quantity How it is computed Sensible W Latent W

    Hour by hour

    Solar hour Sun altitude β ° Sun azimuth φ ° Walls W Roof W Glass: solar W Glass: conduction W Sensible W Latent W Total W

    Azimuth φ is measured from south, positive to the west and negative to the east.

    The surfaces at the peak hour

    Surface Total irradiance E_t W/m² Sol-air t_e °C Heat entering W/m²

    The two air states

    StateOutdoor airRoom air

    Export

    Convert units: Mechanical: HVAC

    Questions engineers ask

    How many tons do I need for my room?

    Enter the room, its exterior walls and windows, the build-up of the walls and roof, and who uses it. The page computes the load at every solar hour of 21 July, takes the highest, adds your margin (10% by default) and converts it at 12,000 Btu/h per ton. A west-facing room gains most in the afternoon, an east-facing one in the morning, and a top-floor room carries its roof as well.

    One unit for several rooms: why is it smaller than the rooms added up?

    Because the rooms do not peak at the same hour: a west room peaks in the afternoon, an east room in the morning. The page adds the rooms hour by hour and sizes the unit on the largest hourly sum, the block load, and shows it beside the sum of each room's own peak. Each room still gets its own peak in the supply air it needs, and the table shows the wall split that room would need on its own, for comparison.

    Why check the T3 capacity and not only the nominal size?

    SASO 2663:2021 rates a unit at T1, 35 °C outdoor, and also tests it at T3, 46 °C outdoor. At 46 °C the same unit delivers less than its nominal rating, and the 0.4% design dry bulb is 45.1 °C in Riyadh and 47.5 °C in Al Ahsa. So the figure to hold against the load per unit is the T3 cooling capacity on the model's specification sheet; enter it and the page says whether it is enough.

    Which unit type does the page suggest?

    Up to 24,000 Btu/h a wall-mounted split; up to 36,000 a wall split or a floor-standing unit; above that a floor-standing, cassette or ducted unit, or more than one unit. You can pick any of the five types and the number of units yourself: the size of each is the smallest nominal step that covers the load divided by the number of units.

    Which cities are listed?

    The 27 Saudi weather stations, in all 13 regions, that have a cooling design table in the 2025 ASHRAE Handbook, Fundamentals, at 0.4%, 1% and 2%: the design dry bulb with its mean coincident wet bulb, and the design wet bulb with its mean coincident dry bulb. Hafr Al Batin is represented by Al Qaisumah. Al Kharj, Al Duwadimi, AlUla and Jubail have weather files but no ASHRAE table, so they are not listed: choose Custom and enter their values.

    Why is the latent load from outdoor air zero in Riyadh?

    At its design dry bulb Riyadh air holds less moisture than a room at 24 °C and 50%, so the air leaking in would dry the room, and the arithmetic gives a negative latent load. The page does not let that lower the size: a negative outdoor-air latent load is taken as zero. People still add their latent heat.

    We do this for a living

    Mechanical

    Mechanical drawings coordinated, priced and formatted for the reviewer who has to approve them.